1 Applied to IBM serverPCworkstation and so on.
2 Applied to automatic control of industrial device and communication.
3 AS400 only provide the interface (dry-contact),users can design the application by themselves.
Install the AS400 Card
1 Open the cover board of intelligent slot, which is at the backboard of the machine. (As the picture below shows, take RACK 3KVA UPS as an example, inside the red circle is the cover board of intelligent slot).
2 Insert AS400 Card in the gap of the intelligent slot, till the metal board in the AS400 card DP-9 communication press very close to the backboard of UPS, then it means the card in the right direction, then fix the card by screws.
3 Connect the AS400card with the monitoring device by cable, then the monitoring device can display and control the UPS working situation, implementing the remote monitoring of the UPS situation.
DB-9 data connecting cable
3The inside interface circuitry of DB-9:
4 The parameter of DB-9 interface electro-pneumatic
Parameter
|
SYMBOL
|
MAX
|
UNIT
|
Diode
|
Reverse Voltage
|
VR
|
6
|
V
|
Forward Current
|
IF
|
80
|
mA
|
Peak Forward Current
|
IF (peak)
|
1
|
A
|
Relay
|
DC Voltage
|
VDC
|
24
|
V
|
DC Current
|
IDC
|
1.0
|
A
|
5 The definition of DB-9 interface pin
DB-9 pin
|
Function
|
Input or Output
|
1
|
UPS Failure
|
Output
|
2
|
Summary Alarm
|
Output
|
3
|
GND
|
|
4
|
Remote Shutdown
|
Input
|
5
|
Common
|
|
6
|
Bypass Active
|
Output
|
7
|
Battery Low
|
Output
|
8
|
UPS ON
|
Output
|
9
|
Utility Failure
|
Output
|
Phenomenon
|
Function
|
Reason
|
PIN1PIN5 connect
|
UPS Failure
|
UPS interior failure
|
PIN2PIN5 connect
|
Summary Alarm
|
1Battery mode 2Battery low mode 3UPS interior failure
|
PIN3
|
GND
|
|
PIN4
|
Remote Shutdown
|
Input remote shutdown signal from outside
|
PIN5
|
Common
|
|
PIN6PIN5 connect
|
Bypass Active
|
UPS bypass mode
|
PIN6PIN5 cut off
|
UPS ON
|
UPS on
|
PIN7PIN5 connect
|
Battery Low
|
Battery Low
|
PIN8PIN5 connect
|
UPS ON
|
UPS on
|
PIN8PIN5 cut off
|
Bypass Active
|
UPS bypass mode
|
PIN9PIN5 connect
|
Utility Failure
|
Utility Failure
|
6The explanation of pin:
7The explanation of AS400
The external monitoring device works as an interface common to provide power below 24v. Take the circuitry below as an example, when each signal port connects with the corresponding signal light and remote shutdown key, then the UPS can be monitored remotely.